Thermal
Right-Sized Cooling for AI Data Center Operators
Independent analysis by Starro. Not client work.

Objective
How Far Single-Phase Cold Plates Can Go
Accelerator packages now dissipate more than 1 kW each. Operators and server builders have to decide how long single-phase liquid cold plates stay adequate, and which upgrade buys the most headroom.
How much power can a single-phase cold plate remove from an AI package before the die passes 85 °C, and where does the temperature budget go?
Findings
The Package, Not the Coolant, Sets the Ceiling
With 30 °C supply and 1.5 L/min, the hottest point of the die stays within 85 °C up to 1.67 kW. Doubling the flow raises this to 1.95 kW and doubles the plate pressure drop.
At 1.4 kW, 24 °C of the 46 °C rise sits in the package (die, interfaces and lid) and 15 °C is the coolant warming along the plate. Removing the lid raises the limit to 2.06 kW with no added flow. Even a perfect coolant would stop at 2.83 kW, because the package uses the rest of the budget.

Approach
Coupled Conduction and Channel Model of a Lidded Package
A representative lidded package (40 × 40 mm heat source, solder TIM1, copper lid, grease TIM2) on a copper microchannel cold plate cooled by 25 % propylene glycol. A three-dimensional conduction model of the stack is coupled to a fin-efficiency model of the channels and an energy balance on the coolant in every channel row.

Validation
Exact, Series and Experimental Benchmarks
How we checked the model:
An exact one-dimensional solution is reproduced to machine precision.
A Fourier-series spreading solution is matched: 20.01 K against 20.06 K.
Heat into the coolant equals the heat applied, to 3 parts in 10¹³.
Grid refinement with Richardson extrapolation: the base grid sits 0.17 K above the extrapolated value.
The classic Tuckerman and Pease microchannel measurement (1981) is matched within 18 %.
Recommendations
Size the Package and the Facility Together
The package, not the coolant, sets the ceiling. Removing the lid buys more than doubling the flow, and supply temperature is the strongest facility lever: at 35 °C and above, 2.0 kW per device is out of reach with this package at any practical flow. Size the facility and the package together.
Tools used:
3D finite-volume conduction model; fin-efficiency channel model; coolant energy balance